AVAILABLE PIPE CLASSES

 

Size
(Nominal)
Outside
Diameter
Pressure &
Special Class
Nominal Wall
Thickness
Pressure
Rating
in mm in mm PC SC in mm p.s.i. kPa
4 100 4.80 121.9 350 -
52
 54*
.25
.29
.35
6.4
7.4
8.9
350
350
350
2410
2410
2410
6 150 6.90 175.3 350 50
52
 54*
.25
.31
.37
6.4
7.9
9.4
350
350
350
2410
2410
2410
8 200 9.05 229.9 350 -
50
52
 54*
.25
.27
.33
.39
6.4
6.9
8.4
9.9
350
350
350
350
2410
2410
2410
2410
10 250 11.10 281.9 350 -
50
52
 54*
.26
.29
.35
.41
6.6
7.4
8.9
10.4
350
350
350
350
2410
2410
2410
2410
12 300 13.20 335.3 350 -
50
52
 54*
.28
.31
.37
.43
7.1
7.9
9.4
10.9
350
350
350
350
2410
2410
2410
2410
14 350 15.30 388.6 250
300
350
-
-
-
50
52
 54*
.28
.30
.31
.33
.39
.45
7.1
7.6
7.9
8.4
9.9
11.4
250
300
350
350
350
350
1720
2070
2410
2410
2410
2410
16 400 17.40 442.0 250
300
350
-
-
50
52
 54*
.30
.32
.34
.40
.46
7.6
8.1
8.6
10.2
11.7
250
300
350
350
350
1720
2070
2410
2410
2410
18 450 19.50 495.3 250
300

350
-
-
50
-
52
 54*
.31
.34
.35
.36
.41
.47
7.9
8.6
8.9
9.1
10.4
11.9
250
300
350
350
350
350
1720
2070
2410
2410
2410
2410
20 500 21.60 548.6 250
300
350
-
50
-
52
 55*
.33
.36
.38
.42
.51
8.4
9.1
9.7
10.7
12.7
250
300
350
350
350
1720
2070
2410
2410
2410
24 600 25.80 655.3 200
250

300
350
-
-
50
-
-
52
 56*
.33
.37
.38
.40
.43
.44
.56
8.4
9.4
9.7
10.2
10.9
11.2
14.2
200
250
250
300
350
350
350
1380
1720
1720
2070
2410
2410
2410
30 750 32.00 812.8 150
200

250
300

350
-
-
50
-
-
52
-
.34
.38
.39
.42
.45
.47
.49
8.6
9.7
9.9
10.7
11.4
11.9
12.4
150
200
200
250
300
300
350
1030
1380
1380
1720
2070
2070
2410
36 900 38.30 972.8 150
200

250
300

350
-
-
50
-
-
52
-
.38
.42
.43
.47
.51
.53
.56
9.7
10.7
10.9
11.9
13.0
13.5
14.2
150
200
200
250
300
300
350
1030
1380
1380
1720
2070
2070
2410
• Pressure ratings shown have an additional 100 p.s.i. (690 kPa) surge allowance.
• Dimensions are subject to manufacturing tolerance.
• * - Recommended classes for grooving.
• Contact Canada Pipe for availability of other Special Classes and larger sizes.

 

SELECT FOR WORKING PRESSURE

The most commonly used classes of Ductile Iron Pipe and their rated working pressures are shown in the adjacent table. All ratings have an additional 100 psi (690 kPa) allowance for surge. A safety factor of 2:1 is then applied to the working pressure and surge allowance.

 

SELECT FOR DEPTH OF COVER

The most commonly used classes of Ductile Iron Pipe for underground installation and their maximum depth of cover are shown in the preceding table. The table is based on single H-20 truckload with a 1.5 impact factor. All classes of Ductile Iron Pipe shown are capable of withstanding loads created under a minimum of 1 ft. (.3 m) of cover, providing a Type 5 laying condition is used. For information on other laying conditions and depths of cover, please contact Canada Pipe.